Home » Products » Generator Sets » DEUTZ Diesel Generator Sets (Water-Cooled) » 253kw DEUTZ Water-cooled Diesel Generator Sets

253kw DEUTZ Water-cooled Diesel Generator Sets / Gensets

  • Specification Data
  • Product Summary
  • Running Condition
Generator-set Diesel Engine (DEUTZ) Alternator (Stamford)
Model 230GF Model BF6M1015C-LA G2A Model HCI4D
Rated prime power 230KW Prime power 256KW Rated power 240KW
standby power 253KW Stand power 285KW Stand power 400V/230V
Rated voltage 400/230V Rated speed 1500rpm Efficiency 93.00%
Rated frequency 415A No. of Cylinder 6 Rated current 433A
Rated currency 50Hz Bore/stroke 132/145 Power factor 0.8
Power factor 0.8 Cylinder arrangement V Frequency 50Hz
Steady state volt deviation ≤±1% Fuel consumption 203g /kwh Protection/ insulation IP23/H
Steady state frequency ≤1.5% Start mode 24V electrical Exciting way brushless self-exciting
Frequency drop scope ≤5% Governor electronic Weight 915kg
Phase three phase Aspiration type Turbocharged inter-cooled
Base Frame steel Cooling way Water cooled
Dimension (mm) 2800×1450×1950 Displacement 11.906L
Weight 3020kg Weight 850kg
Type Generator Set 230GF
Place of Origin China (Deutz License Manufacturer)
Brand Name Deutz Engine
Output Capacity 287 KVA
Output Power 230 kW
Frequency 50Hz/60Hz
Cooling Type Water Cooled
Alternator Meccalte/Stamford/or customerized
Optional silent type /open type/water-proof type
Certification ISO, EURO II
According:GB/T2820;Altitude: 0 ~ 1000m ;Ambient temperature: -35 ~ 40 ℃ ;Relative humidity: 95%

Standard scope of supply
Generator-set assembly(diesel engine, alternator, air filter, oil filter, fuel filter, silencer elbow, battery, Connection lines, circuit breaker, bracket)

Option
base oil tank, independent oil tank, Assistant starting system when low temperature, Intelligent control system.Different alternator brands available. One phase is optional.

Control system function
start and stop function.
Panel: voltage, current, frequency, power factor, power, oil pressure, battery voltage, start times, gen -set running hours, temperature, etc.
Failure protection (alarm and stop) function: over speed/speed signal loss alarm, low oil pressure alarm, high cylinder temperature stop, low battery voltage alarm, stop failure alarm, emergency stop alarm, VAC/frequency over limit alarm, currency/power over load alarm, voltage unstable alarm, currency unstable alarm, belt broken alarm, etc.